The Blower Filter Unit is installed on the ceiling and is a kind of clean unit with a filter and a fan, providing the cleanliness level from Class 100 to Class 100,000.

Each room can operate separately, enabling to minimize the main air control facility. It keeps the exit velocity constant to maintain a high cleanliness level and indoor anti-diffusion.

: Hospital (Operating Room, Dust-Free Room, etc.) and Clean Room (Electronic Semi-Conductor, etc.)


 

  • The unit itself provides clean air.
  • Various cleanliness levels are available depending on how to install or the number of installation(s).
  • A clean room may be built relatively easily regardless of the shape of building.




 

Spec/ Model
SG-BFU1W
SG-BFU2W SG-BFU3W SG-BFU4W

Body
670x670x620H 670x670x750H 670x975x620H 670x1280x750H
Casing and Check Hole: Steel Plate Melamine Coating 1.2t
Punching Plate:Steel Plate Melamine Coating 1.0t or Stainless 1.0t
Sound-Absorbing Material 20t, Finished by a Porous Plate
Filter
Blower Filter DOP Test 99.97% or higher
610x610x150t 610x610x292t 610x915x150t 610x1220x150t
Fan
Turbo Impeller(Backward Wheels)Type
Air Volume(CMM)
17 32 26 35
Sound Level(dB)
35~50
Weight(kg) 28 32 35 45

* The Wind Volume of a Filter is based on the standard filter.
* In addition to the specification above, various types are available according to order.